Grupo de Termotecnia de la Universidad de Valladolid

GIR             Grupo de Investigación Reconocido de la Universidad de Valladolid
UIC 053      Unidad de Investigación Consolidada de Castilla y León

Comparte|Share:

Diseño web: Paula M. Esquivias

Study on environmental quality of a surgical block

Autores/Authors: San José-Alonso, J.F.; Velasco-Gómez, E.; Rey-Martínez, F.J.; Álvarez-Guerra, M.A.; Gallego-Peláez, M.C.
Revista/Journal: Energy and Buildings 1999, 29 (2), 179-187
Fecha Publicación/Publication Date: 23/03/1999
Impacto/Impact: JCR (1999): 0.180    CONSTRUCTION AND BUILDING TECHNOLOGY    Posición/Position: 19/26    Cuartil/Quartile: Q3    Tercil/Tertile: T3
DOI: 10.1016/S0378-7788(98)00058-9

Resumen/Abstract:

This article presents the study of a surgical block with serious deficiencies of Indoor Air Quality (IAQ) located in the Hospital del Rio Hortega (Valladolid, Spain).

Block characteristics were identified and symptoms reports collected from 118 workers. At the end of the initial investigation, it was concluded that there was Sick Building Syndrome. Measurements of ventilation and contaminants were made of indoor air (CO, CO2, TVOC, anaesthetic gases, at six differents points simultaneously) and outdoor air (hospital incinerator).

Studies with trace vapors (Xylene) were also performed on installations which crossed the surgical area to see whether a relationship existed between the different surgical areas studied and other areas of the health centre.

Actions on contaminating foci, climatization-ventilation and personnel training were finally recommended to Administration to solve the problem.

◄Artículos|Articles

Universidad de Valladolid | GIR Termotecnia
Paseo del Cauce nº 59, 47011, Valladolid
Reservado todos los derechos

Investigador Coordinador:
Francisco Javier Rey Martínez
+34 983 42 33 66 | rey@eii.uva.es