Influence of constructive parameters on the performance of two indirect evaporative cooler prototypes

Autores/Authors: Tejero-González, A.; Andrés-Chicote, M.; Velasco-Gómez, E.; Rey-Martínez, F.J.
Revista/Journal: Applied Thermal Engineering 2013, 51(1-2), 1017-1025
Fecha Publicación/Publication Date: 01/03/2013
Impacto/Impact: JCR (2013): 2.624    THERMODYNAMICS    Posición/Position: 6/55    Cuartil/Quartile: Q1    Tercil/Tertile: T1
DOI: 10.1016/j.applthermaleng.2012.10.054

Resumen/Abstract:

Two equally-sized cross-flow heat-exchanger prototypes have been designed with a total heat exchange area of 6 m2 and 3 m2 respectively, constructed with polycarbonate hollow panels of different cross section. They are connected into a heat-recovery cycle within the whole experimental setup constructed for the tests, which mainly consists of: an Air Handling Unit to simulate the outdoor airstream conditions, a conditioned climate chamber, and a water circuit to provide the water supply required.

They have been experimentally characterised in two operating modes in order to determine how evaporative cooling improves heat recovery in each case, focussing on the influence of modifying the constructive characteristics. To perform the evaporative cooling process, water is supplied to the exhaust airstream.

Results are studied considering how constructive issues, outdoor air volume flow rate and temperature, as well as operating mode influence on the performance obtained. An Analysis of Variance shows how outdoor airflow has a key role in the performance of the systems; whereas entering outdoor air temperature determines cooling capacities. Improvements introduced by larger heat exchange areas compensate with their corresponding smaller cross sections, which hinder water-air distribution on the exhaust air side of the heat exchanger. Finally, these small devices achieve cooling capacities of up to 800 W, being able to partly support ventilation load and achieving around 50% of energy saving in ventilation cooling.